FM-200 calculator
Work out how much FM-200 clean agent your room needs and the cylinders to hold it, using the NFPA 2001 total flooding method. Then send the figures to us for a quote.
FM-200 agent quantity calculator
Enter the size of the room to work out how much FM-200 (HFC-227ea) a total flooding system needs, and the cylinders to hold it. Based on NFPA 2001, Standard on Clean Agent Fire Extinguishing Systems.
Your result
| Net protected volume | |
|---|---|
| Design concentration | |
| Specific volume of FM-200 vapour | |
| Altitude correction | |
| FM-200 agent needed rounded up | |
| Cylinders | |
| How it is worked out | |
Your request goes by email to sales@ethiopia.westwoodkenya.com through our contact form, or by WhatsApp to +254 733 276 276.
This is an estimate for planning. The final design (agent quantity, cylinders, pipe network and nozzles) is confirmed by our engineers with a site survey and a hydraulic calculation. It does not allow for openings that cannot be closed.
Fire classes and design concentration (NFPA 2001)
- Class A: fires in ordinary combustible materials such as wood, cloth, paper, rubber and many plastics. FM-200 design concentration 6.7%.
- Class B: fires in flammable liquids, oils, greases, tars, oil-based paints, lacquers and flammable gases. Design concentration: the cup burner value for the fuel x a safety factor of 1.3.
- Class C: fires involving energised electrical equipment, such as server rooms and switch rooms. FM-200 design concentration 7.0%.